ID 442426.04 378WE KEEP THINGS MOVING
Diagnosis
16
Manual SD6
16.10 40:Invalid data
Triggering Level Response Counter
A data error was detected when initializing the
non-volatile memory.
Fault The power board remains switched off and the drive is
torque-free/force-free. If the air override is inactive, a
possibly existing brake will be controlled to close.
Z40
Cause Description Measure Confirmable
1:Error Low level write/read error or timeout. The drive controller must be sent in for
repair. Please contact our Service
department.
No
2:blockMiss Unknown data block
3:dataSecurity Block has no data security.
4:CheckSum Block has a check sum error.
5:R/O Block is r/o.
6:readErr Start-up phase: Block read error
7:blockMiss Block not found
8:Serial number Serial number is incorrect/invalid.
32:el. nameplate No nameplate data available • For STOBER standard motor: Please
contact our Service department.
• For motor from other manufacturers: Set
B06 to 1:arbitrary setting and manually
enter the motor data.
Yes
33:el.typeLim Nameplate parameter cannot be entered
(limit value or existence).
• Check the configuration of the drive
controller and motor.
• Please contact our Service department.