ID 442426.04 190WE KEEP THINGS MOVING
Drive controller
9
Manual SD6
9.5.3.3 45:oTempMot. i2t
Triggering Level Response Counter
The i
2
t model for the motor reaches 100 % load. Parameterized
level in U10:
•Inactive
• Message
• Warning
•Fault
Parameterized fault response in A29:
• A29 = 0:inactive
The power board is switched off and the drive
becomes torque-free/force-free. If the air override is
inactive, a possibly existing brake will be controlled to
close.
• A29 = 1:active
The drive is stopped with a quick stop. If the air
override is inactive, a possibly existing brake will be
controlled to close at the end of the quick stop.
Z45
Possible cause Test Measure Confirmable
The motor is overloaded Check whether the operating conditions
have caused the motor to overheat (load
state, surrounding temperature of the motor,
etc.).
• Take measures to meet the
requirements for the operating
conditions.
• Rectify any existing blockages.
• If necessary, correct the drive design.
Yes