Diagnosis
16
Manual SD6
16.57 *ConfigStartERROR unknown string
16.58 *ConfigStartERROR unknown scale
Triggering Level Response
The versions of configuration and firmware do not
match.
— The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close. The brake chopper is
turned off.
Possible cause Test Measure Confirmable
The configuration saved in the
Paramodule originates from a newer
firmware that recognises more texts
(e.g. name of the system standard
block parameters).
— Apply a suitable configuration or firmware
via DriveControlSuite.
No
Triggering Level Response
The versions of configuration and firmware do not
match.
— The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close. The brake chopper is
turned off.
Possible cause Test Measure Confirmable
The configuration saved in the
Paramodule originates from a newer
firmware that recognizes more
system scaling functions.
— Apply a suitable configuration or firmware
via DriveControlSuite.
No