ID 442426.04 431WE KEEP THINGS MOVING
Diagnosis
16
Manual SD6
16.55 *ConfigStartERROR remanents lost
16.56 *ConfigStartERROR unknown block
Triggering Level Response
No flag values are saved. — The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close. The brake chopper is
turned off.
Possible cause Test Measure Confirmable
The A00 Save values action was not
performed.
— • Apply a suitable configuration via
DriveControlSuite and then save it
(A00).
• Replace the Paramodule.
No
Triggering Level Response
The versions of configuration and firmware do not
match.
— The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close. The brake chopper is
turned off.
Possible cause Test Measure Confirmable
The configuration saved in the
Paramodule originates from a newer
firmware that recognises more
system blocks.
— Apply a suitable configuration or firmware
via DriveControlSuite.
No