ID 442426.04 431WE KEEP THINGS MOVING
Diagnosis
16
Manual SD6
16.55 *ConfigStartERROR remanents lost
16.56 *ConfigStartERROR unknown block
Triggering Level Response
No flag values are saved. The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close. The brake chopper is
turned off.
Possible cause Test Measure Confirmable
The A00 Save values action was not
performed.
Apply a suitable configuration via
DriveControlSuite and then save it
(A00).
Replace the Paramodule.
No
Triggering Level Response
The versions of configuration and firmware do not
match.
The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close. The brake chopper is
turned off.
Possible cause Test Measure Confirmable
The configuration saved in the
Paramodule originates from a newer
firmware that recognises more
system blocks.
Apply a suitable configuration or firmware
via DriveControlSuite.
No