16.61 *ConfigStartERROR unknown pre-rd
16.62 *ConfigStartERROR unknown hiding
Triggering Level Response
The versions of configuration and firmware do not
match.
— The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close. The brake chopper is
turned off.
Possible cause Test Measure Confirmable
The configuration saved in the
Paramodule originates from a newer
firmware that recognises more Pre-
read functions (mapping of firmware
parameters to configuration
parameters).
— Apply a suitable configuration or firmware
via DriveControlSuite.
No
Triggering Level Response
The versions of configuration and firmware do not
match.
— The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close. The brake chopper is
turned off.
Possible cause Test Measure Confirmable
The configuration saved in the
Paramodule originates from a newer
firmware that knows more hide
functions (hide parameters that
should be visible depending on other
parameters).
— Apply a suitable configuration or firmware
via DriveControlSuite.
No