ID 442426.04 114WE KEEP THINGS MOVING
Connection
7
Manual SD6
Terminal description X103B
7.4.6 X103C
X103C specification
Terminal description X103C
Pin Designation Function
5 BA7
Binary output
6 BA8
7 BA9
8 BA10
9 BE6 Binary input
Maximum conductor cross-section
Connection type Maximum conductor cross-section [mm
2
]
Rigid 1,5
Flexible 1,5
Flexible with cable end,
without plastic sleeve
1,5
Flexible with cable end, with
plastic sleeve
0,75
2 leads with the same cross-
section with double cable end
—
Information
When the 24 V power fails, binary inputs BE6 to BE13 have signal
status 0 (regardless of the physical signal state).
General specification
Maximum cable
length
30 m, shielded
Electrical data
Binary inputs
BE7 to BE13
Low level 0–8 V
High level 12–30 V
Input voltage Max. 30 V
Input current Max. 16 mA
Input frequency Max. 3 kHz
Pin Designation Function
10 BE7
Binary input
11 BE8
12 BE9
13 BE10
14 BE11
15 BE12
16 BE13