Parameter list
9836 3123 01 373 (428)
Parameter
number
Parameter name
Description
Default
value
T430
Wear indicator
Enables/disables (on/off) the wear indicator alarm function.
T431
Wear used
For every tightening the wear is calculated through a formula with in-
parameters: torque, speed and temperature etc.
As soon as a tightening or loosening is started, the wear is calculated and
added to T431, which is the accumulated wear since last service.
When the T431 has reached 100%, it's time for service
When the tool has been serviced this parameter is set to 0.
T432
Remaining
tightenings
Estimated number of tightenings that can be performed before wear indicator
alarm occurs.
T433
Alarm factor
Using T433, the customer can scale the effective service interval (time to
wear alarm is activated). In case T433 is set to 25%, the alarm will activate 4
times earlier than by default. In case T433 is set to 400%, the alarm will
activate 4 times later than default.
100%
T434
Min wear
tightenings
An additional condition for activation of wear indicator alarm. Specifies the
minimum amount of tightenings (since latest service) that must be performed
before wear indicator alarm activates.
250000
T440
QRTT on
On/Off
Automatic tool calibration using the ACTA 4000 and a QRTT device is
enabled in this branch. A tool calibration session is started by connecting the
ACTA to the Power Focus and fit the QRTT device to the spindle. One
Multistage with three Psets is used when the calibration is run, one torque
tightening (for torque calibration) and two different rotate spindle (for
loosening and angle calibration) Psets.
It is necessary for the Power Focus to have enough memory space available to
store the Multistages and Psets needed. If the calibration shows an
unsatisfactory result the operator is assumed to take the appropriate action. No
calibration value (calibration- or normalization value etc.) will be changed
automatically.
Off
T441
QRTT Pset 1
Pset used by ACTA.
0
T442
QRTT Pset 2
Pset used by ACTA.
0
T443
QRTT Pset 3
Pset used by ACTA.
0
T444
QRTT Mset
Multistage used by ACTA.
0
T445
Create QRTT
Creates the QRTT Pset and Multistage. Use only when tool is connected.
T450
Perform motor
tuning
When selected, this parameter will perform motor tuning on the connected
tool.
T451
Perform Sync motor
tuning
When selected, this parameter will perform Sync motor tuning on the
connected tools (a Sync group must exist).
T460
Disconnect tool
Disables reading and writing to the tool memory and allows the user to
change tools without power off.

Table of Contents

Other manuals for Atlas Copco Power Focus 3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Atlas Copco Power Focus 3000 and is the answer not in the manual?

Atlas Copco Power Focus 3000 Specifications

General IconGeneral
BrandAtlas Copco
ModelPower Focus 3000
CategoryControl Systems
LanguageEnglish

Related product manuals