Event codes
400 (428) 9836 3123 01
Strategy
configuration
error
No valid control strategy was chosen for
the stored Pset.
Additional parameter information:
First parameter: Pset number
Second parameter: Parameter number
with an incorrect value
Third parameter: Parameter in second
integer is dependent on this parameter
Fourth parameter: Parameter in second
integer violates this limit.
Change control strategy valid for used
tool.
Check that the Pset parameters are
correct and store the Pset.
Not possible to
run a Multistage
with a Click
Wrench Pset
An attempt was made to perform a
Multistage tightening containing at least
one Pset with a click wrench strategy.
Open the Multistage.
Remove the click wrench Pset.
Add an applicable Pset and store the
settings.
Tightening and loosening prohibited
due to missing serial number
Password
Incorrect Input
Source
The password is entered from an invalid
source according to the configuration.
Enter the password from ToolsTalk or
change parameter C801 Entry.
Max time for first
tightening run out
(Job)
This message is displayed and the Job is
terminated if the first tightening is not
performed within the specified time.
If needed, open PF Map > Job >
Timer and change the parameter J320
Maxtime to start Job, or set to 0 to shut
off timer.
Store Job and try again.
Max time to
complete Job run
out
This message is displayed and the Job is
terminated if the Job is not completed
within the specified time in Job
configuration.
If needed, open PF Map > Job >
Timer and change the parameter J321
Maxtime to complete Job, or set to 0 to
shut off timer.
Store Job and try again.
Identifier not
accepted, the
length is not
correct.
The length of the incoming barcode string
is wrong.
Open PF Map > Identifier and check
that the string Length matches the
scanned string, and that the scanned
string does not exceed 100 characters.
Identifier not
accepted, does
not match any
type
The incoming barcode string does not
match any type.
Open PF Map > Identifier and check
Input source, string Length and
Significant position are correctly
configured.
Bypass Identifier
not possible
The Type 1 identifier can not be bypassed
when an optional Type exists.
Open PF Map > Identifier and
remove optional Type if not used.