EasyManua.ls Logo

Azbil C7G

Azbil C7G
426 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-10
Chapter 3. Wiring
Handling Precautions
Connect a terminating resistor (120 Ω, 1/2 W) to both ends of the
communication line. Do not connect a terminating resistor to the middle part
of the communication line.
To connect two terminals together such as SG, use a crimp terminal without
an insulation sleeve.
Be sure to connect the SG terminals to each other. Failure to do so might cause
unreliable communication.
If equipment controller devices that do not allow connection of a terminating
resistor (such as Azbil Corporation's SDC15/25/26/35/36 and DMC10) are
included in the transmission line, do not connect any terminating resistor to
the external or communication lines of the C7G.
The frame ground should be connected to only one end of the shielded cable,
not to both ends.
Analog input block (analog input)
V+
+
-
B
C
A
mA+
Current input Voltage input T/C input RTD input
1 :
2 :
3 :
4 :
5 :
1 :
2 :
3 :
4 :
5 :
1 :
2 :
3 :
4 :
5 :
1 :
2 :
3 :
4 :
5 :
-
Maximum allowable input voltage
Current input: –1.5 to +1.5 V
Voltage input: –15 to +15 V
T/C input: –1.5 to +1.5 V
Handling Precautions
Do not apply a voltage exceeding the allowable maximum input stated in the
specifications to any input. Doing so will cause device failure.
Make the connections while carefully checking the polarity of the inputs.
Use shielded cables for input wiring.
When a thermocouple is used for the input, take appropriate measures so that
no terminals are exposed to moving air. Failure to do so may result in an error.
Set a suitable sensor type for usage. If the setting is incorrect, it will not be
possible to measure the PV correctly, and a hazardous situation could result,
such as a constant 100 % control output.

Table of Contents

Related product manuals