EasyManuals Logo

Azbil C7G User Manual

Azbil C7G
426 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #161 background imageLoading...
Page #161 background image
4-91
Chapter 4. Functions
Linearization by specifying bias
The input values for linear approximation are the breakpoint settings A1 to A10,
the bias values for linear approximation are the breakpoint settings B1 to B10, and
the output values are A1 + B1 to A10 + B10, and these appear as shown in the graph
below.
Input at A1 or before results in output of a value equal to Input value + B1.
Input at A10 or after results in output of a value equal to Input value + B10.
Output
(A + B)
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10
Input (A)
For B1–B10, upward arrows mean a positive value,
and downward arrows mean a negative value.
Example using linear approximation by analog input
This is an example of using linear approximation of one linearization table for
analog input of slot A4.
The input for 0.0 to 100.0 is converted to 0.0 to 100.0 for a separate characteristic.
(1) Specify the groups of the linearization table in the analog input bank.
Item (bank) Display Description Initial value
Linearization table group definition
(Analog input bank)
MENU > AnalogInput
Linearization table group
0: No linearization
1: 1 group Select this
2 to 8: Groups 2 to 8
0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Azbil C7G and is the answer not in the manual?

Azbil C7G Specifications

General IconGeneral
BrandAzbil
ModelC7G
CategoryController
LanguageEnglish

Related product manuals