Page #144 background imageLoading...
Page #144 background image
4-74
Chapter 4. Functions

Linearization table group definition
The setting is valid if the AO-C block is in the A2, B2, A1, or B1 slot.
The linearization table group used for linear approximation of analog output can
be set. It is also possible to combine the linearization table group selection by DI
(digital input).
Item (bank) Display Description Initial value
Linearization table group
definition
(analog output bank)
MENU > AnalogOutput
Linearization table group
0: No linearization
1 to 8
0
Note
• 4 - 16 Linear Approximation (p.4-90) (for details on linearization table
settings)
• If the version of the MAIN block firmware is earlier than 6.x.x (where x stands for
any number), linearization table group definition by DI (digital input) cannot be
used.