6-48
Chapter 6. Display and Setting Data
Segment bank
Bank selection: SEGMENT
Pattern selection: Patterns 1 to 16
Segment selection: Segments 1 to 16
The table below lists the relevant items for one segment. These items are the same
for segments 1 to 16 of patterns 1 to 16.
Segment settings
Item display Item Settings Initial value
Communication
Notes
Read
Write
RAM
EEPROM
SP SP −32000 to +32000 0.0
With decimal
point
Time Time 0 to 30000 0
Time unit of
patterns
PID Group PID group
number
For segment 1, 1 to 8
For segments other
than segment 1, 0 to 8
For segment 1, 1
For segments other
than segment 1, 0
The setting 0
indicates the
same group
number as that
of the previous
segment.
G.SOAK type G.SOAK type 0: No G.SOAK
1: G.SOAK at the
segment end point
2: G.SOAK at the
segment start point
0
G.SOAK width G.SOAK width 0.0000 to 32000 0.0000
With decimal
point
Segment event Segment event 0: No segment event
1 to 16: Segment
event 1 to 16
0
Handling Precautions
If the version of the MAIN block firmware is earlier than 6.x.x (where x stands
for any number), there is no segment bank.
Note
When segment settings are written via communication, RAM and EEPROM (the
normal memory area) are differentiated by the data address. 9 - 5 Pattern
Communication Data (p.9-15)