6-37
Chapter 6. Display and Setting Data

IP ADDRESS bank
Bank selection: IP ADDRESS
Loop selection: None
Group selection: None
Item display Item Settings Initial value
Communication
Notes
Read
Write
RAM
EEPROM
IP address IP address 0.0.0.0 to
255.255.255.255
192.168.255.254 - - -
Subnet mask Subnet mask 0.0.0.0 to
255.255.255.255
255.255.255.0 - - -
Default gateway Default gateway 0.0.0.0 to
255.255.255.255
0.0.0.0 - - -

RS-485 bank
Bank selection: RS-485
Loop selection: None
Group selection: None
Item display Item Settings
Initial
value
Communication
Notes
Read
Write
RAM
EEPROM
Station address Station address 0: No communication
1 to 127
0

-

Transmission speed Transmission speed 1: 9600 bps
2: 19200 bps
3: 38400 bps
4: 57600 bps
5: 115200 bps
2

-

Data type (parity) Data type
(Parity)
0: Even parity
1: Odd parity
2: No parity
0

-

Data type (stop bits) Data type
(Stop bits)
0: 1 bit
1: 2 bits
0

-

Minimum response
time
Minimum response time 1 to 250 ms 3

-
