CHAPTER 7: IEC 61850 PROTOCOL 7.2 IEC 61850 PROFILE FOR F650
GEK-106310-AF F650 DIGITAL BAY CONTROLLER 7-29
2.2 Profile conformance
The following tables define the basic conformance statement.
2.2.1 PICS for A-Profile support
2.2.2 PICS for T-Profile support
Refer to the services of Part 7 to see whether these profiles are supported. No distinction is made between A- and T-
Profiles there because the definition only refers to the application.
2.3 MMS conformance
The following conformance statements are conditional upon the support of the client/server A-Profile (e.g. A1 see profile
description in Clause 6) being declared.
Except where present, MMS conformance shall be in accordance with ISO/ISP 14226-2.
2.3.1 MMS Initiate conformance
2.3.1.1 MMS InitiateRequest general parameters
A-Profile
shortcut
Profile description
Client Server
Value/comment
realized realized
A1 Client/server A-profile N Y
A2 GOOSE/GSE Management A-profile Y Y Only GOOSE not GSE
m
anagement
A3 GSSE A-profile Y Y
A4 Time sync A-profile Y N
A-Profile
shortcut
Profile description
Client Server
Value/comment
realized realized
T1 TCP/IP T-profile N Y
T2 OSI T-profile N N
T3 GOOSE/GSE T-profile Y Y Only GOOSE not GSE
m
anagement
T4 GSSE T-profile Y Y
T5 TimeSync T-profile Y N
InitiateRequest
Client-CR Server-CR
realized Value/range realized Value/range
InitiateRequest
localDetailCalling Y
proposedMaxServOutstandingCalling Y
ProposedMaxServOustandingCalled Y
InitRequestDetail Y
InitiateRequestDetail
proposedVersionNumber Y
proposedParameterCBB Y
servicesSupportedCalling Y
additionalSupportedCalling N
additionalCbbSupportedCalling N
privilegeClassIdentityCalling N

Table of Contents