Diagnosis
16
Manual SD6
16.51 *ParaModul ERROR: file not found
16.52 *ParaModul ERROR: Checksum error
Triggering Level Response
The Paramodule file can not be read. The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close. The brake chopper is
turned off.
Possible cause Test Measure Confirmable
May have been switched off during
the A00 action.
Apply a suitable configuration via
DriveControlSuite and then save it (A00)
Attach a suitable Paramodule.
No
Faulty or unformatted Paramodule Replace the Paramodule. No
Triggering Level Response
A checksum error was detected when loading from
the Paramodule.
The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close. The brake chopper is
turned off.
Possible cause Test Measure Confirmable
Memory bit dumped. Apply a suitable configuration via
DriveControlSuite and then save it (A00).
No