4-57
Chapter 4. Functions
Operation type Operation
type
setting
Direct action
● means that ON/OFF changes at that
value
◯ means that ON/OFF changes after
that value is passed
Reverse action
● means that ON/OFF changes at that
value
◯ means that ON/OFF changes after
that value is passed
Deviation high and low
limits
(Final SP basis)
9
Event
main
setting
Event
subsetting
PV
SP
ON
HYS
ONHYS
Except for the SP ramp, same as the direct
action of the deviation low limit.
During the SP ramp, the action is different
in that the final SP is used instead of the
current SP.
ONHYS
HYS
Event
main
setting
Event
subsetting
PV
SP
Except for the SP ramp, same as the
reverse action of the deviation high limit.
During the SP ramp, the action is different
in that the final SP is used instead of the
current SP.
SP high limit 10
ONHYS
Event main setting
ON
HYS
Event main setting
SP low limit 11
Event main setting
ON
HYS
Event main setting
ONHYS
SP high and low limits 12
Event main
setting *
1
Event
subsetting *
1
ON
HYS
ONHYS
Event main
setting *
1
Event
subsetting *
1
SP
ONHYS
HYS
MV high limit 13
ONHYS
Event main setting
MV
ON
HYS
Event main setting
MV
MV low limit 14
Event main setting
MV
ON
HYS
Event main setting
ONHYS
MV high and low limits 15
Event main
setting *
1
Event
subsetting *
1
ON
HYS
ONHYS
ONHYS
HYS
Event main
setting *
1
Event
subsetting *
1
MFB high and low limits 16
Event subsetting
ON
HYS
ONHYS
ONHYS
HYS
Event subsetting
Standard numerical
code high limit
26
ONHYS
Event main setting
ON
HYS
Event main setting
Standard numerical
code low limit
27
ON
HYS
Event main setting
ONHYS