4-124
Chapter 4. Functions

Virtual AI 1 to 4
Item (bank) Display Description Initial value
Virtual AI assignment
(Virtual analog input bank)
MENU > VirtualAnalogInput
Virtual AI assignment
2048 to 3071: Standard
numerical codes
2048
Filter
(Virtual analog input bank)
MENU > VirtualAnalogInput
Filter
0.0000: No filter
0.0001 to 120.00
0.0000
Ratio
(Virtual analog input bank)
MENU > VirtualAnalogInput
Ratio
0.0010 to 10.000 1.0000
Bias
(virtual analog input bank)
MENU > VirtualAnalogInput
Bias
−32000 to +32000
A maximum of 5 digits, plus 4
digits after the decimal point,
can be set.
0.0000
Linearization table group
definition
(Virtual analog input bank)
MENU > VirtualAnalogInput
Linearization table group
0: No linearization
1 to 8: Groups 1 to 8
0
Handling Precautions
• Virtual AIs and virtual PVs do not have an alarm function. Use the alarm
triggered by the low and high limits of the assignment range for input
assignment.