9-7
Chapter 9. User-defined Addresses
Method 4:
When writing from the SLP-C7 Smart Loader Package, select [Communication]
[C7 Restart] from the menu in the Setup screen of SLP-C7, to restart the C7G,
and then write the data from SLP-C7.
This writing procedure is simple, but the restart interrupts control by the C7G.
Care is also required because operation after the restart starts with the value
written in the normal memory area before the restart.