9-9
Chapter 9. User-defined Addresses
• Alarm (bit field)
The alarm (bit field) items that can be set among the user-defined addresses with
the SLP-C7 are shown below.
Monitor > Alarm Status > Block Failure Alarm (bit field)
Bit15 = MAIN block
Bit14 = DI/DO block
Bit13 = RS-485 block
Bit12 = HMI block
Bit11 to Bit8 = Empty (fixed to 0)
Bit7 = Block B4
Bit6 = Block B3
Bit5 = Block B2
Bit4 = Block B1
Bit3 = Block A4
Bit2 = Block A3
Bit1 = Block A2
Bit0 = Block A1
Monitor > Alarm Status > DO Overcurrent Alarm (bit field)
Bit15 = Empty (fixed to 0)
Bit14 = DI/DO block
Bit13 to Bit8 = Empty (fixed to 0)
Bit7 = Block B4
Bit6 = Block B3
Bit5 = Block B2
Bit4 = Block B1
Bit3 = Block A4
Bit2 = Block A3
Bit1 = Block A2
Bit0 = Block A1
Monitor > Alarm Status > Loop 1 Alarm (bit field)
Bit15 = User-defined alarm
Bit14 to Bit4 = Empty (fixed to 0)
Bit3 = RSP high limit error
Bit2 = RSP low limit error
Bit1 = PV high limit error
Bit0 = PV low limit error