13-9
Chapter 13. Specifications
Loader communications
Dedicated PC loader: SLP-C7FJ91 (free version) or SLP-C7-J91 (paid version)
Recommended cable: USB-Micro USB (type A/B) cable (USB 2.0-supported,
5 m max.) or Ethernet cable
Power supply: When connected with a USB cable, the device can be
powered by the PC and parameters can be changed.
Data storage
SD: microSD/SDHC-compliant (4 GB) (for the compact data
storage and health index functions)
General specifications
Memory backup: EEPROM (durability: 1 million erase-write cycles max.,
for parameter settings)
Power consumption: 25 VA max., 10 W max. (AC models)
12 W max. (DC models)
Power ON inrush current:
25 A max., 10 ms max.
Start delay at power ON: 10 s (required until normal operation begins under
standard conditions)
Allowable transient power loss:
20 ms min. (AC models)
5 ms min. (DC models)
Insulation resistance: 20 MΩ min. (between power supply terminal (#1 or
#2) and frame ground terminal (#3), with a 500 V DC
megger)
Dielectric voltage: AC models
1500 V AC, 1 min
Between AC power supply terminals (#1 or #2) and
frame ground terminal (#3)
Between AC power supply terminals (#1 or #2) and
secondary terminals
Between AC power supply terminals (#1 or #2) and
motor block terminals (#1 to #3
Between motor block output terminals (#1 to #3)
and frame ground terminal (#3)
Between motor block output terminals (#1 to #3)
and secondary terminals (excluding motor block
output terminals (#1 to #3))