13-11
Chapter 13. Specifications

Standard conditions
Ambient temperature: 23 °C −2/+5 °C
Ambient humidity: 60 ±5 % RH
Power voltage: 105 V AC ±10 % (AC models)
24 V DC ±5 % (DC models)
Power supply frequency: 50 Hz ±1 % or 60 Hz ±1 % (AC models)
Vibration: 0 m/s2
Shock: 0 m/s2
Mounting angle: Reference plane ±3° (main unit), no restriction (display
unit: separated from the main unit)
Space: 100 mm min. above and below, left and right, back and
front (main unit); gang mounting acceptable (display unit)

Operating conditions
Ambient temperature: 0 to 50 °C, 0 to 40 °C (when 2 or more main units are
gang-mounted)
0 to 50 °C (display unit)
Ambient humidity: 10 to 90 % RH (without condensation)
Rated power voltage: 100 to 240 V AC (operating input voltage 85 to 264 V AC,
AC models)
24 V DC (operating input voltage 20.4 to 28.8 V DC, DC
models)
Power supply frequency: 50 Hz ±2 % or 60 Hz ±2 % (AC models)
Vibration: 0 to 5 m/s2 (10 to 60 Hz for 2 h each in the x, y, and z
directions)
Shock: 0 to 100 m/s2
Mounting angle:
Reference plane ±10° (main unit), no restriction (display unit)
Elevation: 2000 m max.
Pollution degree: 2
Installation location: Indoors
Space: 50 mm min. above and below
No space is needed around the display unit

Transport/storage conditions
Ambient temperature: −20 to +70 °C
Ambient humidity: 10 to 95 % RH (without condensation)
Vibration: 0 to 10 m/s2 (10 to 60 Hz for 2 h each in the x, y, and z
directions)
Shock: 0 to 300 m/s2 (3 times each in the x, y, and z directions)