1-24
Chapter 1. Overview
Constant value operation: Process control uses the LSP or RSP.
Pattern operation: Process control uses the pattern SP (the SP is generated from the segment setting stored
in the measuring instrument).
RUN: Control execution status (the three statuses of RUN, RUN-HOLD, and RUN-END in
the case of pattern operation)
READY: Control stop status
AUTO: Automatic operation (This controller automatically determines the MV value.)
MANUAL: Manual operation (The MV value can be operated manually.)
LSP: Local SP (The control is performed based on the SP stored into the controller.)
RSP: Remote SP (The analog input from an external device is used as the SP.)
RUN-HOLD: Control status in which pattern progression is stopped
RUN-END: Control status in which pattern progression is stopped at the final point
AT: Auto tuning (The PID constants are set automatically using the limit cycle.)
Handling Precautions
In the case of internal cascade control, it is not possible to switch into pattern
operation.
With internal cascade control, the master side (Loop 1) in constant value
operation is fixed in LSP mode for RUN + AUTO modes. It cannot be switched
to the READY, MANUAL, or RSP mode.
For the function to select RUN or READY at startup, a value stored in EEPROM,
RUN, or READY can be selected by setting "Loop1 Run/Ready at startup" to
"Loop4 Run/Ready at startup" in the basic action bank.
If the version of the MAIN block firmware is earlier than 6.x.x (where x stands
for any number), there is no pattern operation function or Run/Ready at
startup selection function.