110
Solution Ultima 844/862/880 Installation Manual
How To Test The Programming Key Using The Hand Held Programmer
1. Before connecting the hand held programmer onto the pins marked PROGRAMMING KEY,
make sure that the switch on the hand held programmer is in the EXT position and that no
external key has been plugged onto the hand held programmer.
2. Enter the Installer's Programming Mode (i.e..
1234followed by the #button).
Two beeps will be heard and the hand held programmer will display the data currently
programmed in “LOCATION 000”.
3. Plug the programming key onto the pins marked EXTERNAL KEY on the hand held
programmer.
4. Enter command
959followed by the #button.
Two beeps will be heard after the programming key has successfully been tested. If you heard
a long beep after issuing this command, the programming key has become corrupt and will
need to be erased to clear the corrupt data. Refer to Command 964 - Erase Programming Key
on page 113 for more information.
5. Before removing the programming key from the hand held programmer, enter command
960followed by the #button to exit the Installer's Programming Mode. Two beeps will
be heard and the system will now return to the disarmed state.
Failing to exit Installer’s Programming Mode before removing the programming key may
result in corrupting the data in the programming key.
Command 960 - Exit Installer's Programming Mode
This command is used to exit the Installer's Programming Mode after you complete programming the
control panel.
You may exit Installer’s Programming Mode from any location by entering command
960
followed by the
#button. Two beeps will be heard and the system will return to the disarmed state.
When using the remote codepad to program the system, you will notice that the
STAY and AWAY
indicators will extinguish to indicate that you have terminated Installer’s Programming Mode.
Command 961- Reset Control Panel Back To Factory Default Settings
This command will reset the control panel back to the factory default values. Refer to the default
values shown throughout this manual or the programming sheets on pages 275 - 295 for more
information.
You may reset the control panel back to the factory default settings from any location when in
Installer’s Programming Mode. This is achieved by entering command
961 followed by the #
button. Two beeps will be heard and the system will default back to the factory default values.
ISSUE162.DOC Electronics Design and Manufacturing Pty Limited