EasyManua.ls Logo

EDM Solution Ultima 844 - Delay Siren until Transmission Complete; Dialler Options 2; Extend Time to Wait for Handshake from 30 - 55 Seconds; Open;Close Reports for STAY Mode 1 and STAY Mode 2

Default Icon
314 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
22
154 Solution Ultima 844/862/880 Installation Manual
Dialler Options 2
LOCATION 178 0
Option Description
1
Open/Close Reports Only If Previous Alarm
2
Open/Close Reports For STAY Mode 1 and STAY Mode 2
4
Delay Siren Until Transmission Complete
8
Extend Time To Wait For Handshake From 30 To 55 Seconds
Table 72: Dialler Options 2
Open/Close Reports Only If Previous Alarm
This option requires Open/Close reports in “LOCATION 345 - 346” to be enabled on page 189 for it
1
to be effective.
An opening report will be sent to the base station receiver when the system has been disarmed after an
alarm has occurred. When the system has been armed, a closing report will be sent. An opening or
closing report will not report again until the system has registered another alarm condition.
If using a
Solution Ultima 880 control panel that has been partitioned, an Open/Close report will
only be sent on the area that the alarm had occurred.
2
4
8
If the system is disarmed when an alarm occurs, only a closing report will be sent when the
system is next armed.
User codes that have their priority set to “Always Send Open/Close” reports will override this
feature, which means that they will always send open/close reports.
Open/Close Reports For STAY Mode 1 and STAY Mode 2
If open and close reports are required when the system is armed in STAY Mode 1 or STAY Mode 2,
this option will need to be selected.
This option requires Open/Close reports in “LOCATION 345 - 346” to be enabled on page 189 for it
to be effective. When arming in STAY Mode 1 or STAY Mode 2, a “Partial Close” report (Contact
ID Event Code 456) will be sent.
Delay Siren Until Transmission Complete
If this option has been selected, the EDMSAT, horn speaker, bell and strobe outputs will not activate
until the base station receiver has sent a kiss-off back to the control panel after the message has been
sent. If multiple messages are sent, the sirens will activate after the last kiss-off has been sent.
However, the EDMSAT, horn speaker, bell and strobe outputs will activate as soon as a codepad
panic, fire and medical alarms have been activated.
Extend Time To Wait For Handshake From 30 - 55 Seconds
The control panel after dialling the monitoring station will wait approximately 30 seconds for receipt
of a valid handshake tone. The handshake tone indicates to the control panel that it has reached the
monitoring station and can now send its messages. Enabling this option will extend the wait time
from 30 seconds to 55 seconds.
ISSUE162.DOC Electronics Design and Manufacturing Pty Limited