Reporting Information
This section covers features that are involved with the basic house keeping of the system. This
includes monitoring of the zones - whether they are isolated from the system or more importantly that
they are actually operating, the status of both the AC mains and DC power to the system and codepad
generated alarms activated by the user.
Zone Status – Zone Tamper Report
LOCATION 325 - 326 00
Location Description
325
Zone Tamper Report
326
Zone Tamper Restore Report
Table 88: Zone Status – Zone Tamper Report Locations
A “Zone Tamper” report (Contact ID Event Code 144) will be sent when the zone loop using split
EOL resistors (3K3/6K8) with tamper (1K) becomes open circuit. Refer to Option 14 in LOCATION
266 on page 166 for more information.
If you want zone tamper and zone tamper restore reports, program the two locations with any digit
between 1 – 15.
Zone Status – Walk Test Report
LOCATION 327 - 328 00
Location Description
327
Walk Test Report
328
Walk Test Restore Report
Table 89: Zone Status – Walk Test Report Locations
A “Walk Test” report (Contact ID Event Code 607) will be sent when either the installer or Master
Code holder enters walk test mode. Refer to Walk Test Mode on page 74 when using the Installer
Code or Walk Test Mode on page 90 when using the Master Code for more information.
If you want walk test and walk test restore reports, program the two locations with any digit between 1
– 15.