164
Solution Ultima 844/862/880 Installation Manual
Day Alarm Zones
LOCATION 265 0
When programming this location, you will notice that there are four options per location. You may
select one, two, three or all four of these options, however, only one number needs to be programmed.
This number is calculated by adding the option bit numbers together. Program a seven (7) if you
require options 1, 2 and 4 simultaneously (i.e.. 1 + 2 + 4 = 7).
Option Day Alarm Zone
1
Zone 1
2
Zone 2
4
Zone 3
8
Zone 4
Table 76: Day Alarm Zones 1 - 4
Day alarm allows a combination of zones to be monitored while the system is in the disarmed state.
Indications are available via any of the programmable outputs including the codepad buzzer. This
function has been expanded to accommodate latching and non-latching day alarm output event types.
When the system has been armed in AWAY Mode, STAY Mode 1 or STAY Mode 2, zones that have
been programmed as day alarm zones will activate the sirens and dialler just as non day alarm zones
do. When day alarm has been turned on, it will ignore any zone pulse count settings that have been
programmed for that zone (i.e.. Zone pulse count is only relevant when the system has been armed).
Example
An example of a day alarm set up could be the front door of a shop that has a pressure mat or
electronic beam that customers activate as they enter to and from the shop. As the customers walk on
the pressure mat or break the electronic beam, the codepad buzzer will beep.
Day Alarm Resetting
An output that has been programmed for day alarm resetting will operate when a zone programmed
for day alarm has been triggered. The output will reset once the zone has resealed. This will only
occur when the system is disarmed. Refer to Output Event Type - Day Alarm Resetting on page 204
for more information.
Day Alarm Latching
An output that has been programmed for day alarm latching will operate when a zone programmed for
day alarm has been triggered. The
ZONE indicator and the latching output will reset when the
button has been pressed. This will only occur when the system is disarmed. Refer to Output Event
Type - Day Alarm Latching on page 204 for more information.
ISSUE162.DOC Electronics Design and Manufacturing Pty Limited