System Reporting Information 187
RF Supervision Time
LOCATION 337 0
Location Description
337
Increments Of 6 Hours (0 – 90 Hours)
Table 94: Zone Status RF Supervision Time Location
A "RF Supervision Failure" report (Contact ID Event Code 307) will be sent to the base station
receiver when the wireless receiver has not received a signal from any RF wireless zone during the RF
Supervision Time. This report will continue to be sent (according to the frequency of the RF
Supervision Time) until the fault has been rectified.
To clear the fault and stop any further reporting, the zone that registered the fault must be unsealed
and resealed again. Refer to Fault Descriptions on page 53 for more information.
If "RF Supervision Time" reports are not required, program "LOCATION 337" with a zero.
RF Low Battery Report
LOCATION 338 - 339 68
Location Description
338
RF Low Battery Report
339
RF Low Battery Restore Report
Table 95: RF Low Battery Report Locations
A “RF Low Battery” report (Contact ID Event Code 384) will be sent to the base station receiver
when the battery voltage on a wireless zone falls below approximately 2.4V DC. An “RF Low
Battery Restore” report will be sent on the first valid signal after the battery has been replaced.
Electronics Design and Manufacturing Pty Limited ISSUE162.DOC