182 Solution Ultima 844/862/880 Installation Manual
Swinger Shutdown Count For Dialler
LOCATION 324 6
Location Description
324
Swinger Shutdown Count For Dialler (0-15)
Table 87: Swinger Shutdown Count For Dialler Location
This location determines the number of times the dialler can be triggered before any lockout options
will take effect. A minimum of one zone must be programmed for lockout dialler for this location to
be effective. Refer to Zone Options 1 on page 175 to program zones for lockout dialler.
Only alarms triggered from zone inputs will increment the swinger shutdown counter. This means
alarms such as codepad panic, code retries and any other system alarms will not effect the swinger
shutdown count.
While the sirens are operating, the counter for the dialler is only incremented by the first zone that
causes the alarm. Any other zones that are triggered during siren time will not effect the counter.
While the dialler is on line, its counter is only incremented by the first zone that causes the alarm.
Any other zones that are triggered while the dialler is on line will not effect the counter.
When the swinger shutdown count (As programmed in "LOCATION 324") has been reached, all
zones that have been triggered will be locked out according to their individual lockout settings.
If "Lockout Dialler" has been enabled for any zone, the last restore signal will not be sent until
the system or area (If partitioned) has been disarmed.
The Swinger Shutdown Count For Dialler is global to both Area 1 and Area 2 when using a
Solution Ultima 880 control panel that has been partitioned.
Example
All eight zones have been programmed for lockout dialler with a swinger shutdown count of 6. If
zone 1 triggers an alarm, the swinger shutdown count will decrement by one at the time the control
panel makes the call to a swinger shutdown count of 5.
If zone 1 re-triggers the dialler, the swinger shutdown count will be decremented by one to a swinger
shutdown count of 4. If zone 1 re-triggers the dialler 3 more times, the swinger shutdown count will
be 1.
If zone 2 triggers an alarm, the swinger shutdown count will be decremented by one to a swinger
shutdown count of zero, therefore, locking out zone 2 from activating the dialler again until the system
has been reset. However, at this point in time, the swinger shutdown count for the dialler has again a
lockout count of 6 and the process of swinger shutdown for the remaining zones including zone 1
begin again until all zones have been locked out.
ISSUE162.DOC Electronics Design and Manufacturing Pty Limited