124 Solution Ultima 844/862/880 Installation Manual
Alarm Link Options
LOCATION 180 3
Option Description
1
Enable Upload/Download Via Alarm Link
2
Enable Alarm Link Call Back
4
Terminate Alarm Link Connection On Alarm
8
Use External Modem Module (CC811) For Alarm Link Operations
1
2
4
8
Table 52: Alarm Link Options
Enable Upload/Download Via Alarm Link
This option will need to be selected if you require to use the Alarm Link Software (CC816) to
remotely program the control panel. The control panel will not respond to the Alarm Link Software if
this option is not selected. Refer to Alarm Link Software on page 122 for more information.
Enable Alarm Link Call Back
If this option has been selected and a call back telephone number has been programmed, the remote
programming computer must be connected to the telephone line that has been programmed in the call
back telephone number locations. Refer to “LOCATION 159 - 174” on page 147 for more
information.
If this option is not selected, it will allow the installer to connect to their customers control panel from
any remote location when attempting upload/download operations without the need to wait for the
control panel to call back to the remote computer, but still allows the ability for the customer to
initiate the modem call from the codepad when requested by holding down the
6 button. Refer to
Alarm Link Software on page 122 for more information.
Terminate Alarm Link Connection On Alarm
If the control panel is communicating with a remote computer via Alarm Link Software (CC816) and
an alarm has registered, the Alarm Link session will be terminated and the relevant alarm message
will then be sent to the base station receiver.
If an alarm occurs that does not need to report to the base station receiver, the session will not be
terminated. If this option has not been selected and an alarm has registered, the Alarm Link software
will prompt the operator with a “Terminate” or “Continue” message.
Use External Modem Module (CC811) For Alarm Link Operations
If this option has been selected, the control panel will use the external plug-in Module (CC811) for
remote programming operations via the Alarm Link Software (CC816). This option should only be
enabled where the telephone line is susceptible to noise.