Zone Information 175
Zone Options 1
When programming this location, you will notice that there are four options per location. You may
select one, two, three or all four of these options, however, only one number needs to be programmed.
This number is calculated by adding the option bit numbers together. Program a seven (7) if you
require options 1, 2 and 4 simultaneously (i.e.. 1 + 2 + 4 = 7).
Option Description
1
Lockout Siren/Lockout Dialler
2
Delay Alarm Reporting
4
Silent Alarm
8
Sensor Watch
1
Example
2
Table 82: Zone Options 1
Lockout Siren & Lockout Dialler
Lockout means one activation per arming cycle (i.e.. A zone programmed for "Lockout" can only
cause the sirens or dialler to operate once).
When the system is next armed, the zone can cause the sirens and dialler to operate once more.
Restore signals will be sent when the system has been disarmed.
The
Solution Ultima 844/862/880 control panel performs lockout different to most other
control panels in that only the first zone to trigger an alarm condition will be locked out. All other
zones that are triggered during the same siren run time will reset when the sirens reset. This prevents
an intruder from triggering all zones then waiting for the sirens to stop before re-entering the
premises.
All zones are programmed for both lockout siren and dialler. Zone 1 is triggered followed by all other
zones causing the sirens to sound and the dialler to report to the base station receiver. Zone 1 will be
the only zone that stops reporting to the base station receiver because of the first zone to trigger is
locked out. The remaining zones will continue to report if they are triggered again.
Refer to Swinger Shutdown Count For Siren on page 181 to set the number of times the siren will be
allowed to activate before it will be locked out and Swinger Shutdown Count For Dialler on page 182
to set the number of times the dialler will activate before lockout will take effect.
Delay Alarm Reporting
This option will allow the reporting of alarms on selected zones to be delayed to allow the user to
enter their code to cancel alarms that are not required to report. All sounding devices (e.g.: horn
speaker, strobe and bell outputs) will operate as soon as the alarm condition occurs, but the dialler will
not operate until the delay time in “LOCATION 418 – 419” on page 217 has expired.