Compliance Information
L100/L110-Specic
L100 UL Labels
L110 UL Labels
UL Fuse Rangs
Model/Type Reference Rang
L100 (BDL1-3R11) –48 V DC, 7.5 A MAX
L110 (BDL1-3B11) –48 V DC, 6 A MAX
General Compliance
NEBS Level 3:
GR-63-CORE Issue 04 (including Seismic Zone 4
requirements)
GR-1089-Electromagnec Compability (EMC) and Electrical
Safety
GR-3108-Class 1 - Equipment in the Outside Plant (OSP)
GR-1089, Secon 9 (Bonding and Grounding) required
installaon standards:
Installed in a Common Bonding Network (CBN)
Installed in NEBS Level 3 environments, for example, Central
Oces as well as Customer Premise Environment (CPE)
Installed in accordance with a DC-C or DC-I conguraon
GR-1089, R4-16, R4-18 (Intra-Building Lightning Protecon)
Warning: All metallic signaling cables
should be shielded with the shield
grounded at both ends to meet intra-
building lightning requirements.
Warning: The intra-building port(s)
(USER1, USER2, LMP, UTLP, and MAINT)
of the equipment or sub assembly is
suitable for connecon to intra-building
or unexposed wiring or cabling only. The
intra-building port(s) of the equipment