104 Upgrade and Maintenance Manual CX2550/60/70 M4
Basic software procedures
I <CPU#> parameters are "0" for CPU 1 and "1" for CPU 2.
Ê If the error status cannot be reset with the method above, please use the
following procedure for resetting the error counter of all CPUs:
Ê Log in as root.
Ê Enter the commands below, followed by [ENTER]:
1. /etc/init.d/srvmagt stop
/etc/init.d/srvmagt_scs stop
/etc/init.d/eecd stop
/etc/init.d/eecd_mods_src stop
2. cd /etc/srvmagt
3. rm -f cehist.bin
4. /etc/init.d/eecd_mods_src start
/etc/init.d/eecd start
/etc/init.d/srvmagt start
/etc/init.d/srvmagt_scs start
Ê Ensure that all pre-fail / fail status issues have been resolved in ServerView
Operations Manager.
5.2.21 Updating ServerView RAID Manager
For the spare parts of the product compatible parts equal to the original parts
might be used. If an old version of the ServerView RAID Manager is used, the
SSD life monitoring function does not work correctly after replacement. Please
always use the latest version of the ServerView RAID Manager.
http://ts.fujitsu.com/support/
http://www.fujitsu.com/jp/products/computing/servers/primergy/downloads/ (for
Japan)