APPENDIX I: FACTORY DEFAULT CONFIGURATION I.1 FACTORY DEFAULT SETTINGS
GEK-106310-AF F650 DIGITAL BAY CONTROLLER i-13
Snapshot Event generation for switchgear
#5
Snapshot Events
SWGR 5
DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation for switchgear
#6
Snapshot Events
SW
GR 6
DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation for switchgear
#7
Snapshot Events
SW
GR 7
DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation for switchgear
#8
Snapshot Events
SW
GR 8
DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation for switchgear
#9
Snapshot Events
SW
GR 9
DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation for switchgear
#10
Snapshot Events
SW
GR 10
DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation for switchgear
#11
Snapshot Events
SW
GR 11
DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation for switchgear
#12
Snapshot Events
SW
GR 12
DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation for switchgear
#13
Snapshot Events
SW
GR 13
DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation for switchgear
#14
Snapshot Events
SW
GR 14
DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation for switchgear
#15
Snapshot Events
SW
GR 15
DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation for switchgear
#16
Snapshot Events
SW
GR 16
DISABLED N/A [DISABLED – ENABLED]
Setpoint > system setup > miscellanious >
Setting Description Name Default Value Step Range
User
Value
Relay out of service status Relay Out Of Service ENABLED
N/A [DISABLED – ENABLED]
Set to local or remote
Local/Remote
Blocked
OFF
N/A
ON; OFF
Active language on the relay Active Language 0
N/A
[0 : 1]
Setpoint > Protection Elements > Phase Current >
> Phase TOC High > Phase TOC High 1 > Phase TOC High 2 > Phase TOC High 3
> Phase TOC Low > Phase TOC Low 1 > Phase TOC Low 2 > Phase TOC Low 3
Setting Description Name Default Value Step Range
User
Value
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Input type Input PHASOR(DFT) N/A [PHASOR – RMS]
Pickup level Pickup Level 1.00
0.01
A
[0.05 : 160.00]
Curve shape Curve IEEE Ext Inv N/A [See list of curves]
Time Dial TD Multiplier 1.00
0.01
s
[0.00 : 900.00]
Reset type Reset INSTANTANEOUS N/A [INSTANTANEOUS – LINEAR]
Voltage Restraint Voltage Restraint DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
Setpoint > Protection Elements > Phase Current >
> Phase IOC High > Phase IOC High 1 > Phase IOC High 2 > Phase IOC High 3
> Phase IOC Low > Phase IOC Low 1 > Phase IOC Low 2 > Phase IOC Low 3
Setting Description Name Default Value Step Range
User
Value
Function permission Function DISABLED N/A [DISABLED – ENABLED]