CHAPTER 7: IEC 61850 PROTOCOL 7.2 IEC 61850 PROFILE FOR F650
GEK-106310-AF F650 DIGITAL BAY CONTROLLER 7-27
S13 1,2 SetDataSetValues TP N
S14 1,2 CreateDataSet TP N
S15 1,2 DeleteDataSet TP N
S16 1,2 GetDataSetDirectory TP Y
Substitution
S17 1 SetDataValues TP N Ed1 only
Setting group control
S18 1,2 SelectActiveSG TP Y
S19 1,2 SelectEditSG TP Y
S20 1,2 SetEditSGValues TP Y
S21 1,2 ConfirmEditSGValues TP Y
S22 1,2 GetEditSGValues TP Y
S23 1,2 GetSGCBValues TP Y
Reporting
Buffered report control block (BRCB)
S24 1,2 Report TP Y
S24-1 1,2 data-change (dchg) Y
S24-2 1,2 quality-change (qchg) Y
S24-3 1,2 data-update (dupd) N
S25 1,2 GetBRCBValues TP Y
S26 1,2 SetBRCBValues TP Y
Unbuffered report control block (URCB)
S27 1,2 Report TP Y
S27-1 1,2 data-change (dchg) Y
S27-2 1,2 quality-change (qchg) Y
S27-3 1,2 data-update (dupd) N
S28 1,2 GetURCBValues TP Y
S29 1,2 SetURCBValues TP Y
Logging
Log control
S30 1,2 GetLCBValues TP N
S31 1,2 SetLCBValues TP N
Log
S32 1,2 QueryLogByTime TP N
S33 1,2 QueryLogAfter TP N
S34 1,2 GetLogStatusValues TP N
Generic substation event model (GSE)
GOOSE
S35 1,2 SendGOOSEMessage MC Y
GOOSE Control Block
S36 1,2 GetGoReference TP
S37 1,2 GetGOOSEElementNumber TP
S38 1,2 GetGoCBValues TP Y
S39 1,2 SetGoCBValues TP Y
GSSE (Ed2:61850-7-2 Annex C)
S40 1,2 SendGSSEMessage MC N Deprecated
GSSE Control Block (Ed2:61850-7-2 Annex C)
S41 1,2 GetGsReference TP N Deprecated
S42 1,2 GetGSSEDataOffset TP N Deprecated
S43 1,2 GetGsCBValues TP N Deprecated
S44 1,2 SetGsCBValues TP N Deprecated