EasyManua.ls Logo

Honeywell E-Class Series - Page 304

Honeywell E-Class Series
327 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Field Valid Inputs Meaning
bbb Wnx RFID Hexadecimal Operation, where no “n” is an implied 1.
c 0 Not Used, should be 0.
d 0 Not Used, should be 0.
eee xyy
HF: Lock after write, where:
x = 0 Use printer setup to determine if lock is performed.
x = 1 Lock after write.
yy = Not Used
UHF EPC Gen2: Lock after write, where:
x = 0 Use printer setup to determine if lock is performed.
x = 1 Lock after write.
yy = Lock state where “01”is for permalock, “10” for pwd- write lock
or “11” for both states
UHF other tag types: Not Used, should be 000.
ffff 0000 9998
HF: Starting block number to write.
UHF EPC Gen2: Block address where “0001” is EPC data, “0002” is
Tag ID or “0003” is user memory. Using “0000” is for EPC data also
(for backwards compatibility).
UHF other tag types: Not Used, should be 0000.
gggg 0000
HF: Not Used, should be 0000.
UHF EPC Gen2: Data word offset currently only used for read
operation
UHF other tag types: Not Used, should be 0000.
hhhh
Four-digit decimal data
byte count.
Number of bytes to follow (to include all bytes that follow until the
end of the data).
UHF data length must be 8 or 12 for EPC, 8 for Tag ID or multiples
of 2 for user memory sections.
jj…j
Valid ASCII character
string followed by a
termination character.
Data to write to the tag.
UHF data length must be 8 or 12 for EPC, 8 for Tag ID or multiples
of 2 for user memory sections.
Example 1
The following example encodes a HF tag, starting at block 001, with “Datamax <CR>
writes RFID best.” It includes a Byte Count Specifier (the portion in bold), where 0024
284
DPLCommand Reference

Table of Contents

Related product manuals