5. Press the «UP» key.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.4.2 Compressor off
Menu
Venting period : ☐
·········
Holidays : ☑
Active line with deactivated check box
Start : 23.12.12
00:00
Time for start
End : 07.01.13
6. Press Enter to accept the setting.
You may manually adjust the start and end of vacation shut-down (date) in the setting mode.
Adjust the times for start and end (hours and minutes) of the vacation shut-down in the same
manner described in chapter 7.5.1.2 (timing program) for the times of the switching points.
Result You have set a standstill time 23.12.12–07.01.13 for your machine.
7.5.3 Starting the machine remotely (Remote ON/OFF)
If the machine is to be started and stopped remotely, the following settings have to be set:
Overview
■ Make the electrical connection (a spare input for the remote contact is to be found in the elec‐
trical wiring diagram for the machine, DI 1.0 being preferred).
■ Switch machine start to remote mode.
■ Press the «Remote» key.
■ If necessary, activate the «Clock » key and configure the clock program (see section7.5.1.2).
■ If required, assign the remote contact to another input.
■ Press the «Remote» key.
7.5.3.1 Switch machine start to Remote mode
Two methods are available to start the machine remotely:
■ Method A: Starting the machine with the input signal from the remote control center.
■ Method B: Starting the machine from the remote control center in addition to a configured
ON/OFF clock program.
The machine can be started from the remote control center even though the clock is activated
and the program has selected compressor OFF at this point in time.
Precondition The electrical connection has been made.
Password level 2 is activated.
The display shows the operating mode.
1. Press «Enter».
The main menu is displayed.
2. Select the
< Configuration ➙ Compressor start ➙ Compressor on >
menu.
3. Press «UP» repeatedly until
Remote mode
is displayed as active line.
7 Initial Start-up
7.5 Configuring machine start and stop
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
69