The sensor has a measuring range of 0 – 50 m
3
/h.
■ The sensor is operated with 4–20 mA.
7.11.2.1 Selecting the Analog data menu
Precondition Password level 2 is activated.
The electrical connection is made.
1. Select menu
< Configuration ➙ I/O periphery ➙ Analogue values >
(see chapter 7.11).
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.7.2 Analogue values
Menu
▶1 AnMod
Active line
▶2 AI
▶3 AO
2. Press «DOWN» once.
The menu for analog measuring devices is displayed as the active line.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.7.2 Analogue values
Menu
▶1 AnMod
▶2 AI
Active line
▶3 AO
3. Press «Enter».
The menu for pressure transducers, temperature sensors, and freely selectable sensor types is
displayed.
4. Press «DOWN» four times.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.7.2.2 AI
Menu
▶1 AI_p_1
Pressure transducer 1
▶2 AI_p_2
Pressure transducer 2
▶3 AI_T_1
Temperature sensor 1
▶4 AI_T_2
Temperature sensor 2
▶5 AI_I_1
Active line, flow rate sensor
▶6 AI_I_1
Freely selectable sensor type
5. Press «Enter».
Result The
< AI_I_1 >
menu is displayed.
7 Initial Start-up
7.11 Configuring input and output signals
126
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3 9_9450 03USE