5. Press «Enter» to accept the setting.
6. Adjust the switching differential in the same way.
7. If necessary, adjust the values for system setpoint pressure pB in the same manner.
8. Press «Esc» repeatedly to return to the Main Menu.
Configuring the clock program
The clock program for the example is set up using the following switching points: A maximum of 10
switching points are available:
No. Weekday Time System setpoint pressure
01 Mon-Fri 06:30 pA On
02 Mon-Fri 17:00 pB On
Tab. 65 Example switching points
Overview
Set the day of the week for the first switching point.
Set the time for the first switching point
Set the system setpoint pressure for the first switching point
Define further switching points.
Precondition Password level 2 is activated.
The
< Configuration ➙ Pressure settings ➙ Load control >
menu is selected.
Configure the switching program as described below.
Enter the weekday for the first two switching points
1. Press the «DOWN» key repeatedly until
< pA/pB Clock >
is displayed as the active line.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.2.3 Load control
Menu
Local mode pA
·········
Remote mode : pA/pB SC2
Key remote : ☑
------------------------------
▶1 pA/pB Clock
Active line
2. Press «Enter».
The
< pA/pB Clock >
menu is displayed.
3. If you want to delete an existing clock program, press «UP» until
Reset:
is displayed as the
active line.
4. Press «Enter» to switch into setting mode.
The check box will flash.
7 Initial Start-up
7.9 Configuring the machine for master control
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
117