KAESER ESD.2C - Activating the Remote Control Key; Configuring the Controller of Machine 2 as Slave; Setting the Remote Operating Mode

KAESER ESD.2C
413 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7. Press «Enter» to accept the setting.
8. Press «DOWN» four times.
9. Press «Enter» to switch into setting mode.
10. Enter the IP address of the communication partner (slave).
11. Press «Enter» to accept the setting.
7.9.4.3 Configuring the controller of machine 2 as slave
Precondition The electrical connection is made.
The
< Configuration ➙ Pressure control ➙ Pressure settings >
menu option is selected.
Set the switching points pA and pB
1. Select the
< Configuration ➙ Pressure control ➙ Pressure settings >
menu.
The switching point pA is displayed as the active line.
2. Press «Enter» to switch into setting mode.
The display of switching point pA flashes.
3. Use «UP» or «DOWN» to set the required value.
4. Press «Enter» to accept the setting.
5. Press «DOWN» once.
The switching point pB is displayed as the active line.
6. Set the switching point pB in the same manner.
Activating the «Remote control» key
1. Select the
< Configuration ➙ Pressure control ➙ Load control >
menu.
Local mode
line is displayed as the active line.
2. Press «DOWN» three times.
The «Remote control» key is displayed as the active line.
3. Press «Enter» to switch into setting mode.
The check box flashes.
4. Press «UP» to activate the check box.
5. Press «Enter» to accept the setting.
Setting the remote operating mode
1. Select the
< Configuration ➙ Pressure control ➙ Load control >
menu.
Local mode line is displayed as the active line.
2. Press «DOWN» twice.
Remote mode
line is displayed as the active line.
3. Press «Enter» to switch into setting mode.
4. Use «UP» or «DOWN» to set the required value for pA/pB SC2.
5. Press «Enter» to accept the setting.
IP configuration
If the controllers of both machines are linked directly, they must have different IP addresses.
7 Initial Start-up
7.9 Configuring the machine for master control
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
103