7.5.1.3 Activating the «Compressor timer» key
1. Press «UP» repeatedly until
Key clock
is displayed as active line.
2. Press «Enter» to switch into setting mode.
The check box flashes in the active line.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
6 Compressor clock
Menu
Key clock : ☑
Active line with deactivated check box
Reset: ☐
·········
01 Mon-Fri 06:30 on
Switching point 01:
02 Mon-Fri 12:00 off
Switching point 02:
03 Mon-Fri 13:00 on
Switching point 03:
3. Use the «UP» key to activate the check box.
4. Press «Enter» to accept the setting.
5. Press «Escape» repeatedly to return to the main menu.
The «Clock» key is activated and can be used.
6. Press «Clock» to enable the operation with a timing program.
7.5.2 Setting up the holiday period
In addition to the fixed cycles of a timing program or timer, you can also specify a longer lasting
standstill time. For example, you may specify a standstill period for vacation shut-down by defining
the following:
Precondition The display shows the operating mode.
1. Press «Enter».
The main menu is displayed.
2. Select
< Configuration ➙ Compressor start ➙ Compressor off >
.
3. Press «DOWN» repeatedly until
Holidays
is displayed as active line.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.4.2 Compressor off
Menu
Venting period : ☐
·········
Holidays : ☐
Active line
Start : 23.12.12
00:00
End : 07.01.13
4. Press «Enter» to switch into setting mode.
The
check box
flashes.
7 Initial Start-up
7.5 Configuring machine start and stop
68
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3 9_9450 03USE