7.5.4 Activating/deactivating the idle phase (Venting period function)
After receiving the OFF signal from the remote control center, an additional idling phase (Venting
period) can be activated before the machine is stopped completely. The duration of the idling
phase can be timed and/or regulated by internal pressure.
Precondition Password level 2 is activated.
The display shows the operating mode.
1. Press «Enter».
The main menu is displayed.
2. Select the
< Configuration ➙ Compressor start ➙ Compressor off >
menu.
The check box for
"Venting period"
is displayed in the active line.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.4.2 Compressor off
Menu
Venting period : ☐
Actual setting: Venting period deactivated
·········
Holidays : ☐
Start : 01.01.12
00:00
End : 01.01.12
3. Press «Enter» to switch into setting mode.
The check box for the "Venting period" function will flash.
4. Press the «UP» key.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.4.2 Compressor off
Menu
Venting period : ☑
Actual setting: Venting period activated
·········
Holidays : ☐
Start : 01.01.12
00:00
End : 01.01.12
5. Press «Enter» to save the setting.
The check box for the "Venting period" function is activated.
The function can be deactivated in the same manner.
You may also activate the Venting period function by pressing the «OFF» key on the controller.
➤ Press the «OFF» key.
Result The "Venting period" function is activated.
Press the «OFF» key twice to immediately shut the machine off.
➤ Press the «OFF» key twice.
Result The machine is switched off without venting (idle time).
7 Initial Start-up
7.5 Configuring machine start and stop
72
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3 9_9450 03USE