■ Assigning the floating relay contact
■ Setting local operating mode
Establishing the electrical connection
■ Contact A open: SIGMA CONTROL 2 controls with system setpoint pressure pB
■ Contact A closed: SIGMA CONTROL 2 controls with system setpoint pressure pA
■ B 1.1: Pressure switch for system setpoint pressure pB
■ B 1.2: Pressure switch for system setpoint pressure pA
07-S0629
A
-K3
A1
A2
Fig. 34 Machine with pressure switch regulation
A Floating relay contact SIGMA CONTROL 2
➤ Make the electrical connection according to the diagram.
Setting the system setpoint pressure pA and pB.
Precondition Access level 2 is activated,
The electrical connections are made.
1. Select menu
< Configuration ➙ Pressure control ➙ Pressure settings >
(see section 7.4.1).
7 Initial Start-up
7.9 Configuring the machine for master control
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
113