7.5.5 Activating/deactivating and adjusting the "Automatic restart after a power fail‐
ure" function
'Autostart:' is activated as standard.
To avoid overloading the main power supply through several machines starting simultaneously, a
delay period determining the restart of each machine can be entered.
Overview
■ If not activated, enter password for level 2
■ Select the
< Configuration ➙ Compressor start >
menu.
■ Activate/deactivate the restart function
or
set the restart delay.
Precondition Password level 2 is activated.
The
< Configuration ➙ Compressor start >
menu option is selected.
1. Press «Enter».
The
Compressor start
menu is displayed.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.4 Compressor start
Menu
▶1 Compressor on
Active line
▶2 Compressor off
·········
Autostart: : ☑
Automatic restart activated
Target 10 s ¦ Actual 0 s
·········
Deactivating/activating automatic restart
1. Press «DOWN» repeatedly until
Autostart:
is displayed as the active line.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.4 Compressor start
Menu
▶1 Compressor on
▶2 Compressor off
·········
Autostart: : ☐
Automatic restart is deactivated
Target 10 s ¦ Actual 0 s
Set/expiring delay period.
·········
2. Press «Enter» to switch into setting mode.
The check box for the "Autostart" function will flash.
3. Press the «UP» key.
The check box for the "Autostart" function is deactivated.
7 Initial Start-up
7.5 Configuring machine start and stop
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
73