Assigning the input for LOAD remote contact
The input for the LOAD remote contact is preassigned.
Setting is only necessary if you deliberately want to use a different input.
1. Press «DOWN» repeatedly until
Load RC
is displayed as the active line.
2. Press «Enter» to switch into setting mode.
The
digital input
display flashes.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.2.3 Load control
Menu
pA/pB DO DOR 1.04 ☐
·········
Load RC DI 1.13 ok ☑
Active line; standard DI 1.13
loc.-load RC DI 1.09 ☐
·········
Key idle : ☑
3. Use the «UP» or «DOWN» keys to select the input for the LOAD remote contact.
4. Press «Enter» to accept the setting.
5. Activate the check box for
DI 1.13
.
ok
is displayed.
Result The operating mode is now configured.
7.9.5.3 Adjusting pressure increase pE.
➤ Adjust the pressure increase pE as described in section 7.4.2.3.
Further information Detailed information on the pressure parameters is provided in chapter 7.4.2.
7.9.5.4 Activating the «Remote control» key
Precondition Access level 2 is activated.
The
< Configuration ➙ Pressure control ➙ Load control >
menu is selected.
1. Press «UP» repeatedly until
Key remote
is displayed as the active line.
2. Press «Enter» to switch into setting mode.
The check box for
Remote control
flashes.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.2.3 Load control
Menu
Local mode
·········
Remote mode : Load RC
Key remote : ☑
Active line
·········
3. Use the «UP» key to activate the check box.