No. Weekday Time System set-point pressure
03 Mon-Sun 12:00 pA On
04 Mon-Sun 18:00 pB On
Tab. 66 Example for a clock program for equal duty cycling during the day
Variant C: Equal duty cycle during the week
A timer triggers the switch between system set-point pressure pA and system set-point pressure
pB (local operating mode: pA/pB SC2 Clk).
Precondition The setpoint pressure pA/pB is configured the same for both machines.
➤ The clock program is set up using the following switching points:
No. Weekday Time System set-point pressure
01 Mon 00:00 pA On
02 Mon 21:00 pB On
03 Tue 18:00 pA On
04 Wed 15:00 pB On
05 Thu 12:00 pA On
06 Fri 09:00 pB On
07 Sat 06:00 pA On
08 Sun 03:00 pB On
Tab. 67 Example for a clock program for equal duty cycling during the week
7.10 Configuring email
SIGMA CONTROL 2 uses email to send information (messages) to an email address.
For this purpose, an Ethernet connection with an SMTP server is required.
Overview
■ Select the menu
< Communication ➙ Ethernet >
.
■ Configure and activate the email function.
■ Set interval and suppress repeats.
Select menu
1. Select the menu
< Communication ➙ Ethernet >
.
7 Initial Start-up
7.10 Configuring email