KAESER ESD.2C - Configuring Email; Example for a Clock Program for Equal Duty Cycling During the Day; Example for a Clock Program for Equal Duty Cycling During the Week

KAESER ESD.2C
413 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No. Weekday Time System set-point pressure
03 Mon-Sun 12:00 pA On
04 Mon-Sun 18:00 pB On
Tab. 66 Example for a clock program for equal duty cycling during the day
Variant C: Equal duty cycle during the week
A timer triggers the switch between system set-point pressure pA and system set-point pressure
pB (local operating mode: pA/pB SC2 Clk).
Precondition The setpoint pressure pA/pB is configured the same for both machines.
The clock program is set up using the following switching points:
No. Weekday Time System set-point pressure
01 Mon 00:00 pA On
02 Mon 21:00 pB On
03 Tue 18:00 pA On
04 Wed 15:00 pB On
05 Thu 12:00 pA On
06 Fri 09:00 pB On
07 Sat 06:00 pA On
08 Sun 03:00 pB On
Tab. 67 Example for a clock program for equal duty cycling during the week
7.10 Configuring email
SIGMA CONTROL 2 uses email to send information (messages) to an email address.
For this purpose, an Ethernet connection with an SMTP server is required.
Overview
Select the menu
< Communication ➙ Ethernet >
.
Configure and activate the email function.
Set interval and suppress repeats.
Select menu
1. Select the menu
< Communication ➙ Ethernet >
.
7 Initial Start-up
7.10 Configuring email
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
121