Example:
Controller machine 1 (Master mode): 169.254.100.101
Controller machine 2 (Slave mode): 169.254.100.102
1. Select
< Communication ➙ Ethernet ➙ IP configuration >
.
2. Enter IP address for the master.
3. Select
< Communication ➙ Ethernet ➙ Connections ➙ SIGMA CONTROL 2 >
.
4. Press «DOWN» twice.
5. Press «Enter» to switch into setting mode.
6. Use «UP» to set the controller of machine 2 to “Slave”.
7. Press «Enter» to accept the setting.
8. Press «DOWN» four times.
9. Press «Enter» to switch into setting mode.
10. Enter the IP address of the communication partner (master).
11. Press «Enter» to accept the setting.
7.9.5 Configuring for master control using the LOAD remote contact (e.g.,
SIGMA AIR MANAGER BASIC)
Overview
Making the electrical connection for LOAD remote contact
Setting the LOAD remote contact operating mode and assign the input
Adjusting the pressure increase pE, if necessary.
Activating the «Remote control» key
Configuring master control as described below.
7 Initial Start-up
7.9 Configuring the machine for master control
104
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3 9_9450 03USE