The bus master can remotely control the SIGMA CONTROL 2.
7.9.3 Configuring the Profibus interface without SIGMA AIR MANAGER or VESIS
Contact KAESER Service for information on configuring the Profibus interface if Profibus is to
be used.
Overview
■ Selecting the Profibus interface
■ Assigning the slave address
■ If necessary, setting suppression time for bus fault
■ Activating the communications module
■ Assigning an output contact for the bus fault message (spare output can be found in the electri‐
cal diagram)
Precondition Communications module from Profibus DP-V0 retrofit kit is installed.
The electrical connection to the bus master is made.
Access level 2 is activated.
The required data has been provided by KAESER.
The display shows the operating mode.
Selecting the Profibus interface
1. Press «Enter».
2. Press «DOWN» repeatedly until
< Communication >
is displayed as the active line.
3. Press «Enter».
4. Press the «DOWN» key.
The
< Com-Module >
menu is displayed as the active line.
8 9 p s i 0 8 : 1 5 1 6 3 ° F
8 Communication
Menu
▶1 Ethernet
▶2 Com-Module
Active line
Key remote : ☑
7 Initial Start-up
7.9 Configuring the machine for master control
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3