Set the switching points pA and pB
1. Select the
< Configuration ➙ Pressure control ➙ Pressure settings >
menu.
The switching point pA is displayed as the active line.
2. Press «Enter» to switch into setting mode.
The display of switching point pA flashes.
3. Use «UP» or «DOWN» to set the required value.
4. Press «Enter» to accept the setting.
5. Press «DOWN» once.
The switching point pB is displayed as the active line.
6. Proceed as described for switching point pA.
Deactivating the «Remote control» key
1. Select the
< Configuration ➙ Pressure control ➙ Load control >
menu.
Local mode line is displayed as the active line.
2. Press «DOWN» three times.
The «Remote control» key is displayed as the active line.
3. Press «Enter» to switch into setting mode.
The check box flashes.
4. Press «UP» key to deactivate the check box.
5. Press «Enter» to accept the setting.
Setting the times
SIGMA CONTROL 2 provides the following options for selecting times:
■ Clock program, or
■ Timer
1. Decide your desired method.
2. Apply the corresponding settings (table).
7 Initial Start-up
7.9 Configuring the machine for master control
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
101