4. Press «Enter» to switch into setting mode.
The
Reset
check box flashes.
5. Press «UP».
The check box is activated.
6. Press «Enter» to accept the settings.
Result The clock program is now deleted.
Selecting the operating mode
1. Press the «DOWN» key.
2. Press «Enter» and use the «DOWN» or «UP» key to select pA or pB (not required in this ex‐
ample).
3. Set up the remaining switching points in the same way.
The clock program is now finished.
4. Select the pA/pB Clock operating mode, see Section 7.8.3.3.
5. Press «Esc» repeatedly to return to the Main Menu.
7.8.3 Configuring the system pressure setpoint changeover using the clock
Overview
■ Enter access level 2.
■ Delete the old clock configuration, if necessary
■ Set clock periods pA and pB
■ Select starting time for pA or pB.
■ Select the pA/pB Cycle operating mode, see Section 7.8.3.3.
7.8.3.1 Setting clock periods pA and pB
Keep to the order of the configuration. The operating mode pA/pB Cycle must not be activat‐
ed when configuring the timer period.
➤ Configure the clock first and then select the operating mode or select another operating
mode first.
Precondition Password level 2 is activated.
The
< Configuration ➙ Pressure control ➙ Load control >
menu is selected.
1. Press «DOWN» repeatedly until the
Settings
pA
/
pB
menu section is displayed as the active
line.
2. Press «Enter» to switch into setting mode.
pA
flashes.
3. Press the «UP» repeatedly until the desired clock period is displayed as the active line.
7 Initial Start-up
7.8 Configuring the machine for local mode
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
85