Feature Value
Current consumption IOM 3 [A] 1,6
IOM ≙ input/output module
Tab. 17 Power supply specifications
2.1.2.2 Maximum cable lengths
Input/Output Conductor length [ft]
Analog input current (AII),
Analog input resistor (AIR)
Analog output current (AOI)
< 100
Digital input (DI),
Digital output relay (DOR)
< 330
Digital output resistor (DOT) < 100
Tab. 18 Cable lengths
2.1.2.3 Input/output modules – degree of protection
Feature Value
Degree of protection within the machine IP 54
Degree of protection within the control cabinet IP 20
Tab. 19 Degree of protection, IOM
2.1.2.4 Input/output modules – dimensions
Feature Value
Width [in] 4.9
Height [in] 9.8
Depth [in] 1.7
Tab. 20 IOM dimensions
2.1.3 Sensors
Pressure transducer
Feature Value
Output signal [mA] 0/4–20
Connection Twin cable
Tab. 21 Pressure transducer
Resistance thermometer
Feature Value
Sensing resistance (to DIN IEC 751) PT100
2 Technical Data
2.1 SIGMA CONTROL 2 Controller
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
7